Run Time Specifications by Unit

Run Time Specifications by Unit

Fuel Purification System Tank Size versus Run Time

The following table is provided to assist in sizing and setup of FPS-3 through FPS-12 Units




System

Tank Size (Gallons)


Run Time Per Day (HH:MM)


FPS-3


FPS-6


FPS-12


500


0:47


0:23


0:11


1000


1:35


0:47


0:23


1500


2:22


1:11


0:35


2000


3:10


1:35


0:47


2500


3:58


1:59


0:59


3000


4:45


2:22


1:11


4000


6:20


3:10


1:35


5000


7:56


3:58


1:59


6000


(N/R)


4:45


2:22


7000


(N/R)


5:33


2:46


8000


(N/R)


6:20


3:10


9000


(N/R)


7:08


3:34


10000


(N/R)


7:56


3:58


12000


(N/R)


(N/R)


4:45


14000


(N/R)


(N/R)


5:33


16000


(N/R)


(N/R)


6:20


18000


(N/R)


(N/R)


7:08


20000


(N/R)


(N/R)


7:56


25000


(N/R)


(N/R)


9:55


30000


(N/R)


(N/R)


11:54

Calculations
are based on a full tank recirculation occurring twice per week. Run time
is shown per day. FPS PLC based units may be programmed with a 7 day
weekly timer; the run time may be adjusted accordingly if the system is
setup to skip days.

FPS RUN TIME WORKSHEET